- Safety switches with integrated read head and integrated evaluation unit.
- switch-on distance 7 mm
Euchner CMS-R-BZB-01P-AS1 Read heads CMS with reed contacts
SKU:
105094
Categories: Safety Switches, Safety switcheses and tools
Description
Additional information
Brand |
---|
GET A PRICE
To receive a proposal, please send your application to [email protected] and specify the required positions and company details.
Specification
ActuatorAn appropriate actuator to suit the read head selected is required. The dimensions of the actuators are the same as those of the read heads, although the former have no connection cable.
AS-Interface inputs
Evaluation is performed via a safety monitor.
Principle of operationReed contacts are installed in the read head of the safety system CMS. The contact blades on the reed contacts are closed under the influence of the magnetic field from the actuator. The read head only responds to the specific mating component, that is a specific actuator which is allocated to the read head type.
Dimension drawing
Electrical connection ratings
Work area
Reliability values according to EN ISO 13849-1
D0 - D3 | Switch actuated/open |
Design | B |
Material | |
Cable material | PUR |
Housing material | Reinforced thermoplastic (PPS), fully encapsulated |
Weight | |
Net | 0,1 kg |
Ambient temperature | -25 ... 60 °C |
Degree of protection | IP67 |
Mechanical life | 100 x 106 |
Installation orientation | Any, pay attention to marking |
Reaction time | |
After change in the actuation status | max.5 ms |
Connection | Hard-wired encapsulated cable with plug connector M12 |
Cable length | 1 m |
Method of operation | Magnetic, reed contact |
ASi voltage | 30 V 26,5 ... 31,6 V |
ASi operating current | max.30 mA |
ASi slave type | |
According to ASI specification 3.0 | ID code: B |
EA code: 0 | |
ASi data in | |
According to ASI safety at work | D0,D1,D2,D3 |
ASi LED | |
LED red | No data exchange between master and slave |
LED red/yellow alternately flashing | No data exchange between master and slave |
LED red/green alternately flashing | Fault |
LED red flashing | Fault |
LED green | Normal operation |
Switch-on distance | 7 mm |
Assured switch-off distance Sar | max.40 mm |
Center offset | 2,5 mm |
Monitoring of the safety guard position | |
Category | 3 |
Performance Level | PL e |
B10D | 3 x 106 |
PFHD | 4.29 x 10-8 |
Mission time | 20 y |